TEMA Fine Food Office
Cuijk, the Netherlands
Office building
Challenge: ventilation relied largely on windows, with inconsistent indoor air quality and high energy demand (label G, 643 kWh/m²·yr). Solution: room sensors, mechanical ventilation, heat recovery, Maxairea CO₂ filtration and radiator control connected through one intelligent automation layer, with smart control developed with MESH Building Management Solutions. Result: measured data show building-wide P95 CO₂ fell from 942 to 671 ppm (A/B commissioning comparison) and time above 800 ppm from 13.24% to 0.02%, while the official energy label improved from G to C and energy use fell to 224.86 kWh/m²·yr.
MESH Building Management Solutions · Systemair · Van Haren · ABIP